Ultrasonic Flow Meter

Location:Home > Products > Flow > Ultrasonic Flow Meter

Ultrasonic Flow Meter

Wall Mount Type

Model
CSDS-100

Application

● Petroleum

● Chemical industry

● Food

● Electricity

● Water supply

● Drainage

Specification

● Highest zero point stability and accurate measurement

● Highest precision on the basis of individually calibrated ultrasonic transducers and transmitters

● One flow meter for all applications

● No maintenance efforts

● Highest process safety

Standard Design

Principle

Transmit time

Accuracy

士1% (rates > 0.2 mps)

Repeatability

0.2%

Velocity

士 32m/s

Pipe Size

DN15 - 600mm

Display

LCD with backlight, display accumulated flow/heat, instantaneous flow/heat, velocity, time etc.

Signal Output

1 way 4 - 20mA output
1 way OCT pulse output
1 way relay output

Signal Input

3 way 4-20mA input achieve to heat measurement by connecting PT100 platinum resistor

Other Functions

Automatically record the positive,negative,net totalizer flow rate and heat. Automatically record the time of power-on/off and flow rate of the last 30 times.Replenish by hand or read the datas through Modbus communication protocol.
Pipe MaterialCarbon Steel
Stainless steel
Cast iron
Cement pipe
Copper
PVC
Aluminum
FRP
Liner
Straight Pipe SectionUpstream: 10D
Downstream:5D
From the pump:30D
D means outer diameter
Liquid TypesWater
Sea water
Industrial sewage
Acid & alkali liquid
Alcohol
Beer
All kinds of oils which can transmit ultrasonic single uniform liquid
Liquid Temperature-30℃ ~ 90℃ 
Optional  -30℃ ~ 160℃
Liquid TurbidityLess than 10000ppm, with a little bubble
Flow DirectionBi-directional measuring
Net flow/heat measuring
Environment TemperatureMain Unit     -30℃ ~ 80℃,
Transducer:   -40℃ ~ 110℃
Temperature transducer: select on enquiry
Environment HumidityMain Unit     85%RH
Transducer: standard is IP65
Optional  IP68
CableTwisted Pair Line 5m(max 500m)  
RS-485 interface, transmission distance up to 1000m
Power SupplyAC220V
DC24V
Power ConsuptionLess than 1.5W
CommunicationMODBUS RTU RS485
TransducerClamp on type
High temperature clamp on type
Insert type
Inline type

The state of the pipeline for measuring the flow will greatly affect the measurement accuracy, the detector installation location should be selected in a place that meets the following conditions:

1. It must be ensured that the straight pipe section where the probe is installed is: 10D on the upstream side(D is the pipe diameter), 5D or more on the downstream side, and there must be no factors that disturb the fluid(such as pumps,valves, throttles, etc.) in the 30D on the upstream side. And try to avoid the unevenness and welding position of the pipeline under test.

2. The pipeline is always full of liquid, and the fluid should not contain bubbles or other foreign objects. For horizontal pipelines, install the detector within ±45°of the horizontal centerline. Try to choose the horizontal centerline position.

3. When install the ultrasonic flow meter, need to input these parameters:  pipe material,pipe wall thickness and pipe diameter. Fulid type, whether it contains impurities,bubbles, and whether the tube is full.

图片1.png

图片2.png


D: inside diameter of the pipe

Transducers installation

1. V-method Installation

V-method installation is the most widely used mode for daily measurement with pipe inner diameters ranging from DN15mm ~ DN200mm. It is also called reflective mode or method. 

图片3.png


2. Z-method Installation

Z-method is commonly used when the pipe diameter is above DN300mm. 

图片4.png