Ultrasonic Flow Meter
Wall Mount Type
Model
CSDS-100
Application
● Petroleum
● Chemical industry
● Food
● Electricity
● Water supply
● Drainage
Specification
● Highest zero point stability and accurate measurement
● Highest precision on the basis of individually calibrated ultrasonic transducers and transmitters
● One flow meter for all applications
● No maintenance efforts
● Highest process safety
Standard Design
Principle | Transmit time |
Accuracy | 士1% (rates > 0.2 mps) |
Repeatability | 0.2% |
Velocity | 士 32m/s |
Pipe Size | DN15 - 600mm |
Display | LCD with backlight, display accumulated flow/heat, instantaneous flow/heat, velocity, time etc. |
Signal Output | 1 way 4 - 20mA output |
Signal Input | 3 way 4-20mA input achieve to heat measurement by connecting PT100 platinum resistor |
Other Functions | Automatically record the positive,negative,net totalizer flow rate and heat. Automatically record the time of power-on/off and flow rate of the last 30 times.Replenish by hand or read the datas through Modbus communication protocol. |
| Pipe Material | Carbon Steel Stainless steel Cast iron Cement pipe Copper PVC Aluminum FRP Liner |
| Straight Pipe Section | Upstream: 10D Downstream:5D From the pump:30D D means outer diameter |
| Liquid Types | Water Sea water Industrial sewage Acid & alkali liquid Alcohol Beer All kinds of oils which can transmit ultrasonic single uniform liquid |
| Liquid Temperature | -30℃ ~ 90℃ Optional -30℃ ~ 160℃ |
| Liquid Turbidity | Less than 10000ppm, with a little bubble |
| Flow Direction | Bi-directional measuring Net flow/heat measuring |
| Environment Temperature | Main Unit -30℃ ~ 80℃, Transducer: -40℃ ~ 110℃ Temperature transducer: select on enquiry |
| Environment Humidity | Main Unit 85%RH Transducer: standard is IP65 Optional IP68 |
| Cable | Twisted Pair Line 5m(max 500m) RS-485 interface, transmission distance up to 1000m |
| Power Supply | AC220V DC24V |
| Power Consuption | Less than 1.5W |
| Communication | MODBUS RTU RS485 |
| Transducer | Clamp on type High temperature clamp on type Insert type Inline type |
The state of the pipeline for measuring the flow will greatly affect the measurement accuracy, the detector installation location should be selected in a place that meets the following conditions:
1. It must be ensured that the straight pipe section where the probe is installed is: 10D on the upstream side(D is the pipe diameter), 5D or more on the downstream side, and there must be no factors that disturb the fluid(such as pumps,valves, throttles, etc.) in the 30D on the upstream side. And try to avoid the unevenness and welding position of the pipeline under test.
2. The pipeline is always full of liquid, and the fluid should not contain bubbles or other foreign objects. For horizontal pipelines, install the detector within ±45°of the horizontal centerline. Try to choose the horizontal centerline position.
3. When install the ultrasonic flow meter, need to input these parameters: pipe material,pipe wall thickness and pipe diameter. Fulid type, whether it contains impurities,bubbles, and whether the tube is full.


D: inside diameter of the pipe
Transducers installation
1. V-method Installation
V-method installation is the most widely used mode for daily measurement with pipe inner diameters ranging from DN15mm ~ DN200mm. It is also called reflective mode or method.

2. Z-method Installation
Z-method is commonly used when the pipe diameter is above DN300mm.