x

Vortex Flow Meter

Location:Home > Products > Flow > Vortex Flow Meter

Flange Types

Flange Types

Model
CSGB - 300

Application

● Used to liquids, gases and steam

● Chemicals and petrochemicals industry

● Power generation

● Heat supply systems

Specification

● To protect the sensor, 4 piezo-electric crystal encapsulated inside the sensor

● Fully welded SS304 body (optional SS316) 

● Work as BTU meter and measure steam or hot water energy.

● Few power consumption: 24 VDC, 15 Watts maximum

● Variety of signals outputs 

● Up to highest temperature 350℃

Standard Design

Size

DN15-DN300mm

Accuracy

±1.0%

Power Supply

24VDC

Communication

RS485/Hart

Flange Standard

EN1092-1
PN10,PN16,PN25,PN40
ANSI BS16.5  Class 150,300,600  
JIS2220  10K,20K,40
AS2129  Table D,Table E
AS4087  PN16,PN21,PN35

Straight Pipe

Inlet Path ≥ 12D,Outlet Path ≥ 5D

Signal Output

4~20 mA,pulse

Frequency Output

2~3000 Hz

Relative Humidity

≤85%

Explosion-proof

Exia IIC T6 Gb

Ambient Temperature :

40℃~55℃ (Non Ex-proof Place)
-20℃~55℃ (Non Ex-proof Place)

Nominal Pressure

1.6 MPa,2.5 MPa,4.0 MPa

Protection Grade

IP65

Velocity

0.4~7.0 m/s liquid
4.0~60 m/s gas
5.0~70 m/s steam

Body Material

SS304
Optional: SS316

Resistance Coefficient

Cd ≤2.6

Oscillatory Acceleration

≤0.2g

Reynolds Number

2x104~7x106

Dimensions in mm

11.jpg

Caliber
     (mm)

Inner
     D1 (mm)

Length
     L (mm)

Flange Outer  D3 (mm)

Central Dia of
     Bolts Hole B (mm)

Flange Thickness C (mm)

Bolt Hole Diameter D(mm)

Hole No.(N)

25

25

170

125

90

14

19

4

32

32

170

135

100

16

19

4

40

40

190

140

105

16

19

4

50

50

190

155

120

16

19

4

65

65

220

175

140

18

19

4

80

80

220

185

150

18

19

8

100

100

240

210

175

18

19

8

125

125

260

250

210

20

23

8

150

150

280

280

240

22

23

8

200

200

300

330

290

22

23

12

250

250

360

400

355

24

25

12


Flow Range

 Nominal
     DN(mm)

Liquid (t=20℃  ρo=1000kg/m3)   

Gas (t=20℃  101325Pa Air)

 

Standard flow range
     (m3/h) 

Extended Flow Range 
     (m3/h) 

Standard flow range
     (m3/h)

Extended Flow Range
     (m3/h) 

15

0.8-6

0.5-8

6-40

5-50

20

1-8

0.5-12

8-50

6-60

25

1.5-12

0.8-16

10-80

8-120

32

2-20

1.5-25

15-150

10-200

40

2.5-30

2-40

25-200

20-300

50

3-50

2.5-60

30-300

25-500

65

5-80

4-100

50-500

40-800

80

8-120

6-160

80-800

60-1200

100

12-200

8-250

120-1200

100-2000

125

20-300

12-400

160-1600

150-3000

150

30-400

18-600

250-2500

200-4000

200

50-800

30-1200

400-4000

350-8000

250

80-120

40-1600

600-6000

500-12000

300

100-1600

60-2500

1000-10000

600-16000

Installation

The installation of vortex flow meter has higher requirements, to guarantee the better accuracy and working properly. Vortex flow meter installation should keep away from the electric motors, big frequency converter, power cable, transformers, etc.

Do not install in the position where there has bends, valves, fittings, pumps etc, which could cause flow disturbances and influence the measurement.

The front straight pipe line and after straight pipe line should follow below suggestion.


图片2.png


Daily Maintenance

Regular cleaning

The probe is an important structure of the vortex flow meter. If the detection hole of the probe is blocked, or is entangled or wrapped by other objects, it will affect the normal measurement, resulting in inaccurate results;


Moisture-proof treatment

Most of the probes have not undergone moisture-proof treatment. If the use environment is relatively humid or is not dried after cleaning, the performance of the vortex flow meter will be affected to a certain extent, resulting in poor operation;


Minimize external interference

Strictly check the grounding and shielding conditions of the flow meter to ensure the accuracy of the flow meter measurement;


Avoid vibration

There are some parts inside the vortex flow meter. If strong vibration occurs, it will cause internal deformation or fracture. At the same time, avoid the inflow of corrosive liquid.