x

Contact pressure gauge

Location:Home > Products > Pressure > Contact pressure gauge

Bourdon tube pressure gauge with switch contacts
Stainless steel case NS 100 and 160

Model
EC02.010 (bottom connection)
EC02.030 (bottom with case filling)
EC02.050 (back connection)
EC02.070 (back with case filling)

Applications

● Control and regulation of industrial processes

● Monitoring of plants and switching of circuits

● For gaseous and liquid aggressive media that are not highly viscous or crystallising, also in aggressive environments

● Chemical industry, petrochemical industry, power plants, mining, on-/offshore, environmental technology, machine building and general plant construction

Special features

● Up to 4 switch contacts per instrument

● Also available with case filling for high dynamic pressure loads or vibrations Instruments with inductive contacts for use in hazardous areas

● Instruments with contacts for PLC applications

● Instruments optionally available in safety version S3 per EN 837


Description 

Design

DIN 16085

Nominal size in mm

100, 160

Accuracy

1.0

Scale ranges 


0…0.6MPa 至 0…160MPa

other units (e.g. psi, kPa) available

or all other equivalent vacuum or combined pressure and vacuum ranges

Pressure limitation

Steady: Full scale value

Fluctuating: 0.9 x full scale value

Short time: 1.3 x full scale value 

Permissible temperature

Ambient: -20 … +60 °C


Medium:

+200 °C [+392 °F] max. with unfilled instruments

+100 °C [+212 °F] max. with filled instruments

Temperature effect 

When the temperature of the measuring system deviates from the reference temperature (+20 °C): max. ±0.4 %/10 K of full scale value

Ingress protection per IEC/EN 60529

IP65

Process connection  

SS316L

■ G ½ B

■ ½ NPT

■ M20 x 1.5

others on request

Connection location

■ Lower mount (radial)

■ Lower back mount

Case 

Stainless steel

Pressure element 

Stainless steel 316L C-type or helical type 

Movement 

Stainless steel

Dial

Aluminium 

Set pointer 

Aluminium, red

Window 

Laminated safety glass 

Electrical connection

Cable socket PA 6, black

Per VDE 0110 insulation group C/250 V

Cable gland M20 x 1.5

Strain relief

6 screw terminals + PE for conductor cross-section 2.5 mm²

Others on request 

Switch contacts

Magnetic snap-action contact model EC02

■ No control unit and no power supply required

■ Direct switching up to 250 V, 1 A

■ Up to 4 switch contacts per measuring instrument

Specifications for instruments with magnetic snap-action contact model EC02

图片1.png

The recommended setting range of the contacts is 25 ... 75 % of the scale (0 ... 100 % on request). Contact material (standard): Silver-nickel, gold-plated


Setting the contacts 

The recommended minimum clearance between 2 contacts is 20 % of the measuring span. The switch hysteresis is 2 ... 5 % (typical)

图片1.png


Recommended contact load with resistive and inductive loads

图片1.png

Dimensions in mm

Cable socket

图片4.png

Dimensions in mm

Models EC02.010.100, EC02.050.100

Models EC02.010.160, EC010.050.160


Model / Nominal size / Type of contact and switching function / Scale range / Process connection / Connection location / Options